ISA Certified Control Systems Technician (CCST) program

Certified Control System Technicians (CCSTs) calibrate, document, troubleshoot, and repair/replace instrumentation for systems that measure and control level, temperature, pressure, flow, and other process variables.

CCST question

When a controller that possesses integral action receives an error signal for significant periods of time, the integral term of the controller will increase at a rate governed by the _______(1)_______. This will eventually cause the manipulated variable to reach 100 % (or 0 %) of its scale, i.e., its maximum or minimum limits. This is known as ______(2)_______.

The best answer set to fill in the two blanks labeled (1) and (2) above is:

A.         (1) offset; (2) integral wind-up

B.         (1) integral time of the controller; (2) integral wind-up

C.         (1) sample time of the controller; (2) integral start

D.         (1) integral time of controller; (2) derivative time

CCST answer

The correct answer is B, (1) integral time of the controller; (2) integral wind-up. The integral term of the PID control algorithm increases (or decreases) at a rate inversely proportional to the integral time of the controller. Because of the feedback nature of the PID algorithm, as long as an error exists, the controller output will increase or decrease until it reaches a high (100%) or low (0%) limit. This is known as integral (or reset) windup. If a controller is outfitted with an anti-reset windup feature, the output will hold at the high or low limit. If not, the calculated output of the controller can continue to "wind up" or "wind down" beyond those limits.

Answer A is incorrect since the offset is not related to the integral action of a controller on error. Answer C is incorrect because sample time and integral start are not directly responsible for the increase or decrease in controller output calculated by the integral action term in the PID equation. Answer D is incorrect because the derivative time is not the result of saturation of the integral term of the controller at a controller limit.

Reference: Goettsche, L.D. (Editor), Maintenance of Instruments and Systems, 2nd Edition