A hands-on test that sticks out

By Sylvain Millette

Sylvain MilletteMany years ago, I was in a paper mill teaching a "hands-on" loop tuning course. A "hands-on" tuning course involves doing the lab exercises on actual loops. Part of the tuning procedure that I teach is to test the precision of the valve. I always emphasize that tuning is the last thing one does, if the valve suffers from stiction or backlash, because tuning will only make matters worse in automatic.

At the mid-morning mark, I wrapped up the first lecture; it covered identifying and measuring process dynamics, as well as control valve troubleshooting techniques. I next asked my class to choose a loop on which we could test and apply our new-found knowledge. We would then be able to use the result of this test to actually tune the loop. After some searching and debating, one of my students suggested (with a certain gleam in his eyes) what he considered the perfect control loop we could use. The "guinea pig" loop in this case was a cleaner pressure control loop. A cleaner is a piece of process equipment used in the pulp and paper industry. It removes heavy particles, such as sand, from pulp stock through centrifugal action, thereby "cleaning" it.

Moreover, inlet pressure variations affect the cleaner efficiency. After setting up a fast trend on the DCS, we put the controller in manual mode and proceeded to perform bumps on the output. A series of 1% changes proved to be fruitless; the pressure did not react. We then graduated to 5% bumps, and still nothing. Only when we made 10% changes did we see a change in the pressure. It was clear that this valve was ill. We made several more changes in the same direction, and the pressure did react as expected. I began to suspect what sort of illness was afflicting the valve.

Pass the test

In order to prove my theory, we reversed the direction of the step changes. This time, the pressure did not react. In fact, we had to move the controller output a total of 30% in the opposite direction in order to see a change in the pressure. I asked my students what kind of sickness the valve had, and they all made me proud by answering "backlash."

Backlash is one of two major "diseases" that will adversely affect valves. The other valve "sickness" is "stiction," short for static friction. Backlash occurs when a valve has some looseness or "slop" in its linkages. It can be present in the valve positioner, actuator or its linkages. This looseness translates into lost valve precision, which in turn affects control efficiency.

Stiction, on the other hand, comes from friction in the valve assembly. This friction can be present in the valve packing, the actuator, the valve body, and even in the positioner. It is important to note the occurrences of backlash and stiction are not necessarily mutually exclusive. Faulty valves have a direct negative impact on controller efficiency; a valve must be precise within 1% of change. In fact, process control audits have revealed that one third of all control related problems are due to faulty valves. There are no controller tuning methods that will compensate for a bad valve.

Mystery march

But what could be causing such large amount of backlash? The only way to find out was to physically inspect the valve. As we trooped out of the control room into the bowels of the mill, I mentally went through the list of "the usual suspects"—rack-and-pinion actuators and loose feedback connections between the valve stem and the positioner.

After some searching, we finally laid eyes on the valve. The valve in question was a ball valve with a diaphragm actuator. In this type of valve, the actuator provides linear "up-down" motion. This "up-down" motion then transforms into rotary motion via a lever arm that is connected to the valve shaft and ball.

What I saw next is still, to this day, etched my mind. The pin that connected the lever arm to the actuator was missing. In its place, we found a mesh of electrical wire and, you guessed it ... duct tape. The whole knotted mess was holding on for its dear life, in spite of the record holding amount of backlash (unbroken in 16 years). At that moment, someone quipped "I guess that's one more use for duct tape."

Behind the byline

Sylvain Millette is a P.E. at the Angus, Ontario-based Millette Control Engineering Inc. where he is president. His e-mail millette@cois.on.ca.