CAP question
Nonincendive-rated field wiring is allowed to be used in which of the following combinations of hazardous area classifications?
A. Class 1, Division 2 and Class 1, Zone 0
B. Class 1, Division 1; Class 1, Division 2; Class 1, Zone 1 and Class 1, Zone 2
C. Class 1, Division 2; Class 1, Zone 1 and Class 1, Zone 2
D. Class 1, Division 2; Class 1, Zone 2 and Non-hazardous
CAP answer
The correct answer is D. Nonincendive is allowed in Class 1, Division 2; Class 1, Zone 2, and Non-hazardous rated areas. Use in higher hazard areas, such as Division 1, Zone 1, or Zone 0 areas, is not allowed.
Reference: NFPA 70, National Electrical Code 2005 or 2008.