CAP question
What ISA RP12.4 (NFPA 496) defined type of pressurization system will reduce the classification within an enclosure from Division 1 to nonhazardous?
A. Type X
B. Type Y
C. Type Z
D. None
CAP answer
The correct answer is A, Type X.
A Type X pressurization system reduces the classification within the enclosure from Division 1 to nonhazardous and, therefore, permits the use of ignition-capable equipment inside the enclosure.
A Type Y pressurization system reduces the classification within an enclosure from Division 1 to Division 2. A Type Z pressurization system reduces the classification within an enclosure from Division 2 to nonhazardous.
Reference: Ernest Magison; Electrical Instruments in Hazardous Locations, 4th Edition; ISA Press, 1998.